BWTS filter pressure calibration: test the differential, not just two gauges

Updated

Sea Clean can calibrate BWTS pressure instruments and check the differential-pressure indication used for filter control. Specify the complete measurement arrangement so two individual certificates do not leave the calculated differential unchecked.

Key takeaways

  • Pressure tags, ranges and units
  • Differential calculation or transmitter details
  • Connection drawing
  • Required control-function checks

Get it done with Sea Clean

Get a quotation — post@seaclean.no

Send an order request against our quotation

Opens your email app. Add your vessel, equipment, port and required date, then send.

Identify how differential pressure is obtained

The system may use a differential transmitter or calculate a difference from two separate pressure signals. Record instrument tags, ranges, units, process connections and controller scaling. Two individually plausible readings can still produce a misleading difference if one signal uses a different reference, range or offset.

Include process connections in the inspection

Blocked or isolated connections can leave an instrument correctly calibrated but disconnected from the actual process condition. Specify inspection of the agreed impulse or process connections and valve alignment alongside the calibration. Record the initial condition before adjustment so the report explains whether the issue was measurement error, connection condition or configuration.

Verify indication and control function separately

Request instrument calibration results and a separate check of displayed differential and the associated alarm or cleaning command where included. Sea Clean can provide a combined package with clear instrument identities and test conditions. Avoid treating an alarm simulation as a substitute for calibration of the actual sensor.

Illustrative procurement scenario

A filter starts cleaning too frequently although both gauges look reasonable. The order includes paired-signal and controller-difference checks as well as calibration, allowing the cause to be identified across the complete measurement path.

Get it done with Sea Clean

Sea Clean carries out annual instrument calibration across EC BWTS manufacturers and variants, with calibration certificates and clearly defined checks. Send the instrument register, due dates and vessel schedule to arrange the work.

Sea Clean services around 400 vessels and supplies around 2,000 kits per year. Get BWTS service, annual calibration, spare parts and water-testing coordination organised through one technical contact.

Email the checklist below with your vessel, equipment and required date. We will quote the defined work or supply. To proceed, reply with the quotation reference and purchase-order details so scope, price and arrangements can be confirmed.

Service and attendance: Arrange BWTS service, calibration and testing

Frequently asked questions

Are two pressure certificates enough?

They document the individual instruments. Add the calculated-differential and control checks if the objective is to verify filter behaviour as well.

Sources

Related articles

Sea Clean BWTS service desk · All Insights